Unidrive M753 M753-02400060A10100AB101 Variable Frequency Drive
CTRL TECHNIQUES M753 Fr.02 RUN 0.0Hz 6.0A 0kW 2.2 kW 400V 6.0A
M753-02400060A10100AB1
Representative image
2.2 kW
Power
400V
Supply
6.0A
Output current
Fr.02
Frame

M753-02400060A10100AB101
2.2 kW 400V Compact VFD

2.2 kW / 3 HP 400V Supply 6.0A Output Frame 02 CompactRegenerativeSTO PL-e
ℹ️
M753 — Compact Regenerative Drive with PL-e Safety
The M753 adds 4-quadrant regenerative operation and an enhanced safety suite (STO, SS1, SS2, SLS, SBC — PL-e/SIL 3) to the compact M750 platform. 400V 3-phase only. Ideal for hoist, press, and cobot applications requiring energy recovery and full safety compliance.

Quick answer: The M753-02400060A10100AB101 is a Control Techniques Unidrive M753 rated at 2.2 kW (3 HP) for 380–480V ±10%, 3-phase supply with 6.0A output. Compact Drive with Enhanced Safety and Regenerative Capability. Frame 02, IP20.

Technical Specifications

Electrical
Model NumberM753-02400060A10100AB101
SeriesUnidrive M753
Power Rating2.2 kW (3 HP)
Output Current6.0 A
OverloadNormal Duty (110% / 60 s)
Supply Voltage380–480V ±10%, 3-phase
Output Frequency0–3,200 Hz
Mechanical
Frame SizeFrame 02
Dimensions (H×W×D)H: 200 mm × W: 70 mm × D: 170 mm
ProtectionIP20 / UL Type 1
Ambient Temperature-10°C to +50°C
Safety & Communications
Safety FunctionsSTO, SS1, SS2, SLS, SBC — PL-e / SIL 3
CommunicationsProfinet + EtherNet/IP (AB101/AB100); Profibus optional

Quick Quote

Formal RFQ Form
24-hour quote response
FOB / CIF / DDP available
English / Russian / Chinese

Applications

  • Compact hoist and servo press drives
  • High-cycle packaging machinery (energy recovery)
  • Precision winding axes with safety requirements
  • Collaborative robot (cobot) drives with full safety suite
  • Medical and pharmaceutical process drives

Common Fault Codes & Remedies

Applicable to CT M753 series. Isolate supply before investigating.

Fault Name Cause & Remedy
Err 3OvercurrentCheck for output short circuit or undersized drive. Increase acceleration ramp (Pr 0.03).
Err 7OvervoltageRegenerative load without braking resistor, or deceleration too fast. Add braking resistor or extend decel ramp.
Err 4UndervoltageSupply voltage below threshold. Check incoming supply and verify stability under load.
Err 15Drive overtemperatureHeatsink overheated. Check ambient temp (max 40°C), clean filter, verify fan operation.
Err 23Motor overtemperaturePTC thermistor tripped or I²t limit exceeded. Check for mechanical jam, verify motor cooling.
Err 46STO activeSafe Torque Off input opened. Check safety circuit wiring to STO terminals.
Err 27Supply lossInput phase loss. Check supply connections and incoming fuses/breaker.
Err 1Phase loss (output)Open circuit on output — motor cable disconnected. Check motor connection and cable.
Err 29Brake IGBT faultBraking IGBT over-temperature. Check braking resistor connection and resistance value.

Related M753 Models

View All M753 Models →

Frequently Asked Questions

Ready to order M753-02400060A10100AB101?

24-hour competitive quote with lead time. DDP delivery worldwide.