Quick answer: The M702-04400150A10100AB100 is a Control Techniques Unidrive M702 rated at 7.5 kW (10 HP) for 380–480V ±10%, 3-phase supply with 15.0A output. High-performance AC/Servo Drive with Integrated EMC Filter. Frame 04, IP20.
| Electrical | |
| Model Number | M702-04400150A10100AB100 |
| Series | Unidrive M702 |
| Power Rating | 7.5 kW (10 HP) |
| Output Current | 15.0 A |
| Overload Capability | Normal Duty (110% / 60 s) |
| Supply Voltage | 380–480V ±10%, 3-phase |
| Output Frequency | 0–3,200 Hz (M702) / 0–1,000 Hz (C200/C300) |
| Mechanical | |
| Frame Size | Frame 04 |
| Dimensions (H×W×D) | H: 340 mm × W: 145 mm × D: 205 mm |
| Protection Rating | IP20 / UL Type 1 |
| Ambient Temperature | -10°C to +50°C (derate above 40°C) |
| Storage Temperature | -40°C to +60°C |
| Safety & Communications | |
| Safety Functions | STO, SBC, SS1, SS2, SLS — PL-e / SIL 3 (same as M700) |
| Communications | Profinet IRT + EtherNet/IP standard (AB100); optional EtherCAT, PROFIBUS |
Applicable to Control Techniques M702 series. Always isolate supply before investigating faults.
| Fault | Name | Cause & Remedy |
|---|---|---|
| Err 3 | Overcurrent | Output short circuit or undersized drive. Check motor wiring, increase acceleration ramp (Pr 0.03), verify drive current rating ≥ motor FLC. |
| Err 7 | Overvoltage | Regenerative load without braking resistor, or deceleration too fast. Add braking resistor, increase deceleration time (Pr 0.04). |
| Err 4 | Undervoltage | Supply voltage below threshold. Check incoming supply, verify supply stability under load. |
| Err 15 | Drive overtemperature | Heatsink overheated. Check ambient temp (max 40°C), clean filters, verify fan operation, reduce switching frequency. |
| Err 23 | Motor overtemperature | PTC thermistor tripped or motor I²t limit exceeded. Check for mechanical jam, verify motor cooling, check PTC wiring. |
| Err 27 | Supply loss | One or more input phases lost. Check supply connections, verify 3-phase symmetry, check incoming fuses. |
| Err 46 | STO active | Safe Torque Off input opened. Check safety circuit wiring to STO terminals, verify safety relay output. |
| Err 1 | Phase loss (output) | Open circuit on output — motor cable disconnected. Check motor connection and cable continuity. |
| Err 12 | Fieldbus timeout | Profinet / EtherNet/IP communication lost. Check Ethernet cable, verify PLC watchdog settings, check IP configuration. |
| Err 29 | Brake IGBT fault | Braking IGBT over-temperature or short circuit. Check braking resistor connection and resistance value. |